Fine gauge copper strand, acc. to VDE 0259, class 5, (bare or tinned copper).
Lead insulation: rubber, coloured, acc. to VDE 0293-308.
Sheath: rubber EM2 acc. to EN 50363-2-1.
Self-extinguishing and flame retardant acc. to VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1.
Flexible conductor, at high mechanical stress in dry and damp rooms, also outdoors.
According to the Low Voltage Directive 2014/35/EU.
G = with protective conductor
Deliverable as cut goods.
Bending radius | flexible use: 8 x outer diameter |
Rated voltage U0 /U | 450/ 750V |
Temperature range | flexible: -25°C up to +60°C fixed installation: -30°C up to +60°C |
Description |
---|
H07RN-F 3G1.0 (051234) Heavy rubber cable, lead colour/no. according to VDE 0293, outside diameter approx. 8.3 to 10.7mm, weight approx. 130 kg/km, copper approx. 29 kg/km |
H07RN-F 3G1,5 L0005 (051238) Heavy rubber hose line, lead colour/no. according to VDE 0293, outside diameter approx. 9.2 to 11.9mm, weight approx. 165 kg/km, copper approx. 43 kg/km, 5m ring |
H07RN-F 3x2.5 (051367) Heavy rubber hose line, lead colour/no. according to VDE 0293, outside diameter approx. 10.9 to 14.0mm, weight approx. 235 kg/km, copper approx. 72 kg/km |